INCH = MM
0.472 11.99
0.250 6.35
0.236 5.99
0.187 4.75
0.130 3.30
0.079 2.01
0.020 0.51
Publication No: US-NP-RS-004 • March 2008
Range Summary
3 www.enersys.com
TERMINAL ILLUSTRATION
LAYOUT ILLUSTRATION
43
2
1
7
8 9
6
5
Faston Tab: 187
Charging
• Standby use: Apply constant voltage charging at 2.275 volts
per cell (or 2.25–2.30VPC).
• Cyclic use: Apply constant voltage charging at 2.40-2.50 VPC.
Initial charging current should be set at less than 0.25CA.
• Top charge: Product in storage (ambient temperature 25°C/77°F)
requires a top charge every six months. Apply constant voltage at
2.40 volts per cell, initial charging current should be set at
less than 0.1CA for 15 to 20 hours.
Discharge
• Stop operation when voltage has reached the minimum
permissible voltage. Recharge immediately.
• Do not operate at 6CA or more current continuously.
Storage
• Always store battery in a fully charged condition.
• If battery is to be stored for a long period, apply a recovery
top-charge every 6 months.
• Store batteries in a dry and cool location.
Temperature
• Keep within ambient temperatures of –15°C to +50°C
for both charging and discharging.
Incorporating battery into equipment
• Encase battery in a well ventilated compartment.
• Avoid installing battery near heated units such as a transformer.
• House the battery in the lowest section of the equipment
enclosure or rack to prevent unnecessary battery temperature rise.
Others
• Avoid terminal short circuit.
• DO NOT expose to open flame.
• Avoid setting batteries in environments which can cause
direct contact to gasoline, paint thinner, organic solvents,
synthetic resins, oil, etc.
Faston Tab: 187 Faston Tab: 250
M5 Bolt Fastened Terminal
INCH = MM
0.250 6.35
0.187 4.75
0.124 3.15
0.098 2.49
0.059 1.50
0.031 0.79
0.020 0.51
0.004 0.10
INCH = MM
0.313 7.95
0.250 6.35
0.180 4.57
0.098 2.49
0.059 1.50
0.031 0.79
0.020 0.51
0.004 0.10
INCH = MM
0.472 11.99
0.453 11.51
0.217 5.51
0.079 2.01
A B
C
D
INCH = MM
0.709 18.01
0.551 14.00
0.256 6.50
0.236 5.99
M6 Bolt Fastened Terminal
M6 Threaded ReceptacleM5 Threaded Receptacle
INCH = MM
0.530 13.46
0.420 10.67
0.310 7.87
0.230 5.84
0.160 4.06
E F
G H
JST No. VHR-2N
INCH = MM
0.870 22.01
0.550 13.97
0.430 10.92
0.230 5.84
INCH = MM
1.100 27.94
0.910 23.11
0.510 12.95
0.390 9.91
0.330 8.38
INCH = MM
1.024 26.01
0.910 23.11
0.430 10.92
0.335 8.51
0.315 8.00
INCH = MM
0.860 21.84
0.530 13.46
0.430 10.92
0.295 7.49
M10 Bolt Fastened Terminal
Tyco. 1-480318-0
M8 Bolt Fastened Terminal
“Camcorder” Terminal
I
J
K
L
INCH = MM
0.806 20.47
0.760 19.30
0.690 17.53
0.630 16.00
0.394 10.01
0.335 8.50
Note:
Dimensions are in inches (mm)
Tolerances are
± 0.02 in. for dimensions < 5mm
± 0.04 in. for dimensions ≥ 5mm
± 0.08 in. for all height dimensions
unless otherwise specified.